Itron
The i value lets us know what volume it is reading per pulse. For example, KLF : 1 means 1 m3 per pulse for this meter.
Connection
Remove the lid of the box by unscrewing the 4 screws on top
Unscrew the cap of the gland and remove the rubber grommet found inside.
Pass the cap of the gland through the water meter cable and then pass the rubber grommet afterwards.
Pass the cable of the meter through the gland into the inside of the box.
Now that the wires are inside the package they are to be connected to the board through the green connector. Hold down connector buttons to open and release the individual connections. Connect wires according to the figure below.
Brown | Green | Yellow | Grey | Red | Black |
---|---|---|---|---|---|
GND | Tamper | Direction Flag | Count | 3V | GND |
Count logs each pulse from the water meter.
This meter is able to detect forward and reverse flow using the Directional flag.
The tamper wire lets you know if the if the device has been removed or wires cut.
We recommend configuring your device by downlink next.